NEC Conductor Ampacity & Voltage Drop Sizer
Determine minimum copper or aluminum AWG size using NEC Table 310.16, NEC 110.14(C) terminal temperature limits, NEC 240.4(D) small-conductor rules, and NEC Chapter 9 Table 8 voltage drop.
Circuit Parameters
NEC Table 310.16 & Chapter 9 Table 8 Complete Reference (14 AWG – 4/0 AWG)
30°C Ambient / Not more than 3 current-carrying conductors| Size | Area (CM) | Cu 60°C | Cu 75°C | Cu 90°C | Al 60°C | Al 75°C | Al 90°C | 240.4(D) Cu Max |
|---|---|---|---|---|---|---|---|---|
| 14 AWG | 4,110 | 15 A | 20 A | 25 A | — | — | — | 15 A max |
| 12 AWG | 6,530 | 20 A | 25 A | 30 A | 15 A | 20 A | 25 A | 20 A max |
| 10 AWG | 10,380 | 30 A | 35 A | 40 A | 25 A | 30 A | 35 A | 30 A max |
| 8 AWG | 16,510 | 40 A | 50 A | 55 A | 30 A | 40 A | 45 A | Ampacity-governed |
| 6 AWG | 26,240 | 55 A | 65 A | 75 A | 40 A | 50 A | 55 A | Ampacity-governed |
| 4 AWG | 41,740 | 70 A | 85 A | 95 A | 55 A | 65 A | 75 A | Ampacity-governed |
| 3 AWG | 52,620 | 85 A | 100 A | 115 A | 65 A | 75 A | 85 A | Ampacity-governed |
| 2 AWG | 66,360 | 95 A | 115 A | 130 A | 75 A | 90 A | 100 A | Ampacity-governed |
| 1 AWG | 83,690 | 110 A | 130 A | 145 A | 85 A | 100 A | 115 A | Ampacity-governed |
| 1/0 AWG | 105,600 | 125 A | 150 A | 170 A | 100 A | 120 A | 135 A | Ampacity-governed |
| 2/0 AWG | 133,100 | 145 A | 175 A | 195 A | 115 A | 135 A | 150 A | Ampacity-governed |
| 3/0 AWG | 167,800 | 165 A | 200 A | 225 A | 130 A | 155 A | 175 A | Ampacity-governed |
| 4/0 AWG | 211,600 | 195 A | 230 A | 260 A | 150 A | 180 A | 205 A | Ampacity-governed |
How PanelSpec Computes Wire Gauge & Voltage Drop
Conductor selection requires checking three sequential constraints rather than looking up one ampacity column in isolation:
- Governing Temperature Column (NEC 110.14(C)): Even when installing 90°C insulated wire such as THHN/THWN-2, circuit breaker lugs and residential panel terminals are normally rated at 75°C (or 60°C for Type NM-B cable per NEC 334.80). The calculator enforces the lower of the conductor insulation rating and equipment termination rating.
- Small-Conductor Overcurrent Limits (NEC 240.4(D)): Copper conductors rated 14 AWG, 12 AWG, and 10 AWG are capped at 15A, 20A, and 30A overcurrent devices respectively in general branch wiring, even though their 75°C/90°C ampacity values read higher.
- Circular-Mil Voltage Drop Check: Using NEC Chapter 9 Table 8 circular-mil areas and standard resistivity constants (K = 12.9 for copper, K = 21.2 for aluminum), PanelSpec automatically recommends stepping up one or more wire sizes when one-way distance drives voltage drop past your 3% branch or 5% feeder target.
Need deeper background on why 6 AWG Romex cannot supply a 60A EV charger circuit? Read our detailed guide on NEC Table 310.16 and the 75°C Terminal Trap.