400A (Class 320) Service with Dual HVAC, Pool & Dual 48A EVs
Models a 4,500 sq ft all-electric residence with dual-zone heat pumps, electric pool heating, sauna, induction kitchen, and two dedicated 48A EV chargers.
Calculated NEC 220.82 Summary
240V Split-Phase Dwelling| Line Item | Code Basis | Factor | Net VA |
|---|---|---|---|
| General Lighting & Receptacles (4,500 sq ft × 3 VA) | NEC 220.82(B)(1) | General Pool | 13,500 |
| Small Appliance (3 × 1,500 VA) + Laundry (2 × 1,500 VA) | NEC 220.82(B)(2) | General Pool | 7,500 |
| Fixed & Fastened Appliances (Range, Dryer, Water Heater, Kitchen, Pool) | NEC 220.82(B)(3) | General Pool | 60,820 |
| General Pool Demand (First 10 kVA @ 100% + Remainder @ 40%) | NEC 220.82(B) | 100% / 40% | 38,728 |
| Heat Pump + 65% Aux Electric Strip | NEC 220.82(C) | 100% Largest HVAC | 19,350 |
| Level 2 EV Charger (48A @ 240V) | NEC 2023 220.57 | 100% Nameplate | 11,520 |
| Total Calculated Service Load | 290 A | 69,598 VA | |
Profile Specifications & Key Findings
Typical Dwelling: 4,500 sq ft home, dual heat pump zones, pool/spa heater, sauna, dual 48A EVSEs
Recommended Hardware Pathway: Class 320 / 400A meter main feeding two 200A panels via parallel 2/0 Cu or 4/0 Al risers
Conductor Sizing Note: 400A residential service typically splits into dual 200A disconnects using parallel 2/0 Cu or 4/0 Al per NEC 310.12.
- Large all-electric residences with simultaneous 96 A of dedicated EVSE load, dual HVAC, and pool heating pass ~245 A total demand, exceeding 200A cleanly into 400A territory.
- Splitting the 400A meter base into two 200A panels allows logical separation: main house loads in Panel A, EVs + pool + garage in Panel B.
- Even on 400A, modeling total demand upfront prevents utility transformer upsize surprises.
When a 400A (Class 320) Service Is Genuinely Justified
While most standard single-family homes fit comfortably on 200A with sensible appliance sizing, large estates exceeding 4,000 sq ft with multiple HVAC zones, electric resistance pool/spa equipment, and unmanaged dual 48A EV chargers routinely calculate between 235 A and 290 A under NEC 220.82.
Balancing Loads Across Dual 200A Service Disconnects
Most Class 320 residential installations land utility service conductors on a 320A continuous (400A max) meter socket feeding two side-by-side 200A main-breaker panels. Keeping each panel under ~140 A calculated load ensures balanced phase loading and ample future expansion.