400A (Class 320) Service with Dual HVAC, Pool & Dual 48A EVs

Models a 4,500 sq ft all-electric residence with dual-zone heat pumps, electric pool heating, sauna, induction kitchen, and two dedicated 48A EV chargers.

400A & Subpanels PASS (Within Capacity)

Calculated NEC 220.82 Summary

240V Split-Phase Dwelling
Total Demand
290 A
69,598 VA
Service Rating
400 A
72.5% used
Headroom
+110 A
Min 400A
EVSE Demand
11,520 VA
NEC 2023 220.57
Line Item Code Basis Factor Net VA
General Lighting & Receptacles (4,500 sq ft × 3 VA) NEC 220.82(B)(1) General Pool 13,500
Small Appliance (3 × 1,500 VA) + Laundry (2 × 1,500 VA) NEC 220.82(B)(2) General Pool 7,500
Fixed & Fastened Appliances (Range, Dryer, Water Heater, Kitchen, Pool) NEC 220.82(B)(3) General Pool 60,820
General Pool Demand (First 10 kVA @ 100% + Remainder @ 40%) NEC 220.82(B) 100% / 40% 38,728
Heat Pump + 65% Aux Electric Strip NEC 220.82(C) 100% Largest HVAC 19,350
Level 2 EV Charger (48A @ 240V) NEC 2023 220.57 100% Nameplate 11,520
Total Calculated Service Load 290 A 69,598 VA

Profile Specifications & Key Findings

Typical Dwelling: 4,500 sq ft home, dual heat pump zones, pool/spa heater, sauna, dual 48A EVSEs

Recommended Hardware Pathway: Class 320 / 400A meter main feeding two 200A panels via parallel 2/0 Cu or 4/0 Al risers

Conductor Sizing Note: 400A residential service typically splits into dual 200A disconnects using parallel 2/0 Cu or 4/0 Al per NEC 310.12.

  • Large all-electric residences with simultaneous 96 A of dedicated EVSE load, dual HVAC, and pool heating pass ~245 A total demand, exceeding 200A cleanly into 400A territory.
  • Splitting the 400A meter base into two 200A panels allows logical separation: main house loads in Panel A, EVs + pool + garage in Panel B.
  • Even on 400A, modeling total demand upfront prevents utility transformer upsize surprises.

When a 400A (Class 320) Service Is Genuinely Justified

While most standard single-family homes fit comfortably on 200A with sensible appliance sizing, large estates exceeding 4,000 sq ft with multiple HVAC zones, electric resistance pool/spa equipment, and unmanaged dual 48A EV chargers routinely calculate between 235 A and 290 A under NEC 220.82.

Balancing Loads Across Dual 200A Service Disconnects

Most Class 320 residential installations land utility service conductors on a 320A continuous (400A max) meter socket feeding two side-by-side 200A main-breaker panels. Keeping each panel under ~140 A calculated load ensures balanced phase loading and ample future expansion.