200A Main Service + 600 sq ft All-Electric ADU Subpanel

Combines a 1,900 sq ft primary residence (gas heat/water) with a new 600 sq ft all-electric backyard ADU subpanel to verify 200A service feasibility.

400A & Subpanels PASS (Within Capacity)

Calculated NEC 220.82 Summary

240V Split-Phase Dwelling
Total Demand
134.2 A
32,200 VA
Service Rating
200 A
67.1% used
Headroom
+65.8 A
Min 150A
EVSE Demand
7,680 VA
NEC 2023 220.57
Line Item Code Basis Factor Net VA
General Lighting & Receptacles (2,500 sq ft × 3 VA) NEC 220.82(B)(1) General Pool 7,500
Small Appliance (4 × 1,500 VA) + Laundry (2 × 1,500 VA) NEC 220.82(B)(2) General Pool 9,000
Fixed & Fastened Appliances (Range, Dryer, Water Heater, Kitchen, Pool) NEC 220.82(B)(3) General Pool 19,300
General Pool Demand (First 10 kVA @ 100% + Remainder @ 40%) NEC 220.82(B) 100% / 40% 20,320
Central A/C Cooling (Gas/Fuel Heat) NEC 220.82(C) 100% Largest HVAC 4,200
Level 2 EV Charger (32A @ 240V) NEC 2023 220.57 100% Nameplate 7,680
Total Calculated Service Load 134.2 A 32,200 VA

Profile Specifications & Key Findings

Typical Dwelling: 1,900 sq ft main house (gas) + 600 sq ft all-electric ADU + 32A EVSE

Recommended Hardware Pathway: Single 200A main service feeds 100A ADU feeder cleanly under combined load math

Conductor Sizing Note: 100A feeder to detached ADU (120 ft run) typically uses 2 AWG Al SER/XHHW-2 (90A) or 1 AWG Al (100A) with 4-wire EGC + grounding electrode.

  • Adding ADU living area (600 sq ft = 1,800 VA) and compact ADU appliances into the 40% general pool adds relatively modest demand (~22–28 A).
  • Check local AHJ rules on whether an ADU requires a separate utility meter or can feed from a 100A subpanel on the main 200A service.
  • Long backyard trench feeders need a voltage drop check alongside NEC Table 310.16 ampacity sizing.

Combining Main Dwelling and ADU Loads on One 200A Meter

When local zoning permits feeding an Accessory Dwelling Unit (ADU) from the primary dwelling 200A service, total combined square footage and fastened appliances must fit inside the 200A rating. Using compact ADU equipment (mini-split heat pump, 24-inch induction range, 120V heat pump water heater, ventless combo washer/dryer) keeps additional load low.

Note that feeder conductors between the main panel and detached ADU are sized using the full 75°C column of NEC Table 310.16 rather than the 83% whole-dwelling discount unless the feeder supplies the entire single dwelling.

Feeder Conductor & Grounding Essentials for Detached Structures

A detached ADU subpanel requires a 4-wire feeder (two hots, isolated neutral, equipment grounding conductor) plus a local grounding electrode system (two ground rods per NEC 250.32). Use the PanelSpec Wire & Voltage Drop tool to confirm trench length stays under 3% voltage drop.