200A Panel + Detached Garage Workshop Subpanel (150 ft Run)
Combines dwelling service headroom with a detached workshop subpanel feeding woodworking tools and EV charging over a 150-foot trench run.
Calculated NEC 220.82 Summary
240V Split-Phase Dwelling| Line Item | Code Basis | Factor | Net VA |
|---|---|---|---|
| General Lighting & Receptacles (2,100 sq ft × 3 VA) | NEC 220.82(B)(1) | General Pool | 6,300 |
| Small Appliance (2 × 1,500 VA) + Laundry (1 × 1,500 VA) | NEC 220.82(B)(2) | General Pool | 4,500 |
| Fixed & Fastened Appliances (Range, Dryer, Water Heater, Kitchen, Pool) | NEC 220.82(B)(3) | General Pool | 22,600 |
| General Pool Demand (First 10 kVA @ 100% + Remainder @ 40%) | NEC 220.82(B) | 100% / 40% | 19,360 |
| Central A/C Cooling (Gas/Fuel Heat) | NEC 220.82(C) | 100% Largest HVAC | 4,200 |
| Level 2 EV Charger (40A @ 240V) | NEC 2023 220.57 | 100% Nameplate | 9,600 |
| Total Calculated Service Load | 138.2 A | 33,160 VA | |
Profile Specifications & Key Findings
Typical Dwelling: 2,100 sq ft home + detached garage workshop with 240V shop equipment & 40A EVSE
Recommended Hardware Pathway: 100A garage subpanel with 1 AWG Cu or 1/0–2/0 AWG Al feeder upsized for <3% voltage drop at 150 ft
Conductor Sizing Note: At 150 ft one-way, an 80A load on 2 AWG Al drops 3.82 V (1.59%) at 240V, while 120V circuits drop 3.18% unless neutral-balanced.
- Trench length matters most for 120V shop receptacles and high-inrush table saws/compressors: 100 ft+ runs benefit from upsizing aluminum feeders one gauge.
- On a 200A home with gas heat, adding 6,000 VA of shop circuits plus a 40A EVSE leaves comfortable headroom (~48 A remaining).
- Always keep neutral and ground isolated in the garage subpanel and drive local ground rods per NEC 250.32.
Balancing Shop Equipment Diversity With EV Charging
Home woodshops and garages often list dozens of amps of motor nameplate ratings (table saw, planer, dust collector, welder) that only run one or two machines at a time. Including a realistic 6,000 VA continuous shop allowance in the main panel calculation alongside a 40A EVSE totals roughly 149 A on a 200A service.
Subpanel Feeder Voltage Drop Over Long Runs
Because aluminum XHHW-2 or SER/USE-2 cable is inexpensive per foot compared to copper, upsizing a 150-foot trench feeder from 2 AWG Al to 1/0 AWG Al or 2/0 AWG Al reduces voltage sag during motor startup for very little extra material cost.